106 Appendix A – CoE Object Dictionary
1010 0 Store parame-
ters
U8 R Write value
0x65766173 into a rel-
evant subindex to save
NVS object values.
1 Save all param-
eters
U32 RW Save the communica-
tion and device profile
areas.
2 Save comm pa-
rameters
U32 RW Save objects
1000…1FFF (commu-
nication profile area).
3 Save appl pa-
rameters
U32 RW Save objects
6000…9FFF (std. de-
vice profile area).
1011 0 Restore default
parameters
U8 R Write value
0x64616F6C into a rel-
evant subindex to re-
store the default values
to NVS objects.
1 Restore all de-
faults
U32 RW Restore the default val-
ues to the communica-
tion and device profile
areas.
2 Restore comm
defaults
U32 RW Restore objects
1000…1FFF (commu-
nication profile area).
3 Restore appl
defaults
U32 RW Restore objects
6000…9FFF (std. de-
vice profile area) which
are saved to the FBA.
Index SI Name Type Ac-
cess
Information NVS