38 Start-up
30 MAPPING FILE
VER
Read-only. Displays the fieldbus adapter
module mapping file revision stored in the
memory of the drive in decimal format.
N/A
ACS355:
FILE CONFIG REV
ACSM1:
MAPPING FILE
VER
ACS850/ACS880/
ACS580:
Mapping file ver
Mapping file revision
31 D2FBA COMM STA Read-only. Displays the status of the fieldbus
adapter module communication.
Note: The value names may vary by drive.
0 = Idle
OR
4 = Off-
line
ACS355:
FBA STATUS
ACSM1:
D2FBA COMM STA
ACS850/ACS880/
ACS580:
D2FBA comm sta
0 = Idle Adapter is not configured.
1 = Exec.init Adapter is initializing.
2 = Time out Time-out has occurred in the communication
between the adapter and the drive.
3 = Conf.err Adapter configuration error: The major or
minor revision code of the common program
revision in the fieldbus adapter module is not
the revision required by the module or
mapping file upload has failed more than
three times.
4 = Off-line Adapter is off-line.
5 = On-line Adapter is on-line.
6 = Reset Adapter is performing a hardware reset.