Name Type Default Description
93_IEF BOOLEAN 0 Information number 93, earth-fault trip, stage high
ARINPROG BOOLEAN 0 Autorecloser in progress (SMBRREC- INPROGR)
FLTLOC BOOLEAN 0 Faultlocator faultlocation valid (LMBRFLO-
CALCMADE)
4.1.5.4 Settings
PID-6864-SETTINGS v1
Table 17: I103FLTPROT Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 128 Function type (1-255)
4.1.5.5 Supported information types
Function status fault protection for IEC 60870-5-103, I103FLTPROT
GUID-E9DF9410-F570-4F85-9063-C76D1D4A0668 v6
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each input signal.
Table 18: I103FLTPROT supported functions
INF Description TYP GI COT
64 Start phase L1 2 Y 1,7,9
65 Start phase L2 2 Y 1,7,9
66 Start phase L3 2 Y 1,7,9
67 Start residual current IN 2 Y 1,7,9
68 Trip general 2 N 1,7
69 Trip phase L1 2 N 1,7
70 Trip phase L2 2 N 1,7
71 Trip phase L3 2 N 1,7
72 Back up trip I>> 2 N 1,7
73 Fault location in ohm 4 N 1,7
74 Forward/line 2 N 1,7
75 Reverse/busbar 2 N 1,7
76 Signal transmitted 2 N 1,7
77 Signal received 2 N 1,7
78 Zone 1 2 N 1,7
79 Zone 2 2 N 1,7
80 Zone 3 2 N 1,7
81 Zone 4 2 N 1,7
Table continues on next page
1MRK 511 394-UEN A Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC 33
Communication protocol manual