4.2.6.2 Function block
GUID-031C0F49-BEBD-40FE-A33F-18F1D94BB4B0 v1
I103POSC MDV
BL OCK
POSITION
IEC15000081-2-en.vsdx
IEC15000081 V2 EN-US
Figure 18: I103POSCMDV function block
4.2.6.3 Signals
PID-6578-INPUTSIGNALS v5
Table 46: I103POSCMDV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of command
POSITION INTEGER 0 Position of controllable object
4.2.6.4 Settings
PID-6578-SETTINGS v6
Table 47: I103POSCMDV Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type
InfNo 160 - 209 - 1 160 Information number for command output
4.2.6.5 Supported information types
IED commands with position for IEC 60870-5-103, I103POSCMDV
GUID-EDA379DC-73E7-48C5-AC3B-A6CA969F351F v2
Number of instances: 50
The function type for each function block instance is selected with the parameter
FunctionType
.
The information number must be selected for the command output.
Table 48: Each I103POSCMDV has one INF forming one command
INF Inst 1 Inst 2 Inst 3... Inst 10 Type COT Purpose Comment
Base 160 161 162 169 1 1,7,9 Position Current
position
1MRK 511 394-UEN A Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC 49
Communication protocol manual