5.3.3.6 Auto-reclosure indications in monitor direction
GUID-88F9AFD6-6464-4DE1-AECB-595142BDCDB3 v2
Table 59: Auto-reclosure indications in monitor direction
INF Semantics Supported
128 CB ‘on’ by AR Yes
129 CB ‘on’ by long-time AR No
130 AR blocked Yes
5.3.3.7 Measurands in monitor direction
GUID-E3942660-0822-447E-BD4E-40D7C5088712 v3
Table 60: Measurands in monitor direction
INF Semantics Supported
144 Measurand I Yes
145 Measurands I, U Yes
146 Measurands I, U, P, Q Yes
147 Measurands I
N
, U
EN
Yes
148 Measurands I
L1,2,3,
U
L1,2,3,
P, Q, f Yes
5.3.3.8 Generic functions in monitor direction
GUID-5F1B0569-3017-4642-BE64-19A2729DDE3D v2
Table 61: Generic functions in monitor direction
INF Semantics Supported
240 Read headings of all defined groups No
241 Read values or attributes of all entries of one
group
No
243 Read directory of a single entry No
244 Read value or attribute of a single entry No
245 End of general interrogation of generic data No
249 Write entry with confirmation No
250 Write entry with execution No
251 Write entry aborted No
5.3.4 Selection of standard information numbers in control
direction
5.3.4.1 System functions in control direction
GUID-2B4161BF-D245-4B25-9ED5-B185926E889F v2
Table 62: System functions in control direction
INF Semantics Supported
0 Initiation of general interrogation Yes
0 Time synchronization Yes
1MRK 511 394-UEN A Section 5
Interoperability
670 series 2.2 IEC 59
Communication protocol manual