4.1.7.2 Function block
GUID-69C2C974-2D64-4174-9F9A-15383C09050D v1
IEC10000293-1-en.vsd
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293 V1 EN-US
Figure 11: I103SUPERV function block
4.1.7.3 Signals
PID-3976-INPUTSIGNALS v5
Table 22: I103SUPERV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
32_MEASI BOOLEAN 0 Information number 32, measurand supervision of
I
33_MEASU BOOLEAN 0 Information number 33, measurand supervision of
U
37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up
protection
38_VTFF BOOLEAN 0 Information number 38, fuse failure VT
46_GRWA BOOLEAN 0 Information number 46, group warning
47_GRAL BOOLEAN 0 Information number 47, group alarm
4.1.7.4 Settings
PID-3976-SETTINGS v5
Table 23: I103SUPERV Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
4.1.7.5 Supported information types
Supervision indications in monitor direction, I103SUPERV
M11874-171 v7
Indication block for supervision in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for output signals.
Section 4 1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
36 670 series 2.2 IEC
Communication protocol manual