ABB IEC 60870-5-103 - IED Status for IEC 60870-5-103 I103 IED; Functionality; Function Block; Signals

ABB IEC 60870-5-103
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INF Description TYP GI COT
82 Zone 5 2 N 1,7
83 Zone 6 2 N 1,7
84 Start general 2 Y 1,7,9
85 Breaker failure 2 N 1,7
86 Trip measuring system phase L1 2 N 1,7
87 Trip measuring system phase L2 2 N 1,7
88 Trip measuring system phase L3 2 N 1,7
89 Trip measuring system neutral N 2 N 1,7
90 Over current trip, stage low 2 N 1,7
91 Over current trip, stage high 2 N 1,7
92 Earth-fault trip, stage low 2 N 1,7
93 Earth-fault trip, stage high 2 N 1,7
4.1.6 IED status for IEC 60870-5-103 I103IED
4.1.6.1 Functionality
GUID-52AC7D0F-33C5-46FC-983E-5CB4B3517D88 v1
I103IED is a function block with defined IED functions in monitor direction. This
block uses parameter as FunctionType, and information number parameter is
defined for each input signal.
4.1.6.2 Function block
GUID-421D5C37-27A5-476A-A7D9-40E70AFDFDC8 v1
I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-2-en.vsd
IEC10000292 V2 EN-US
Figure 10: I103IED function block
4.1.6.3 Signals
PID-3975-INPUTSIGNALS v5
Table 19: I103IED Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
19_LEDRS BOOLEAN 0 Information number 19, reset LEDs
21_TESTM BOOLEAN 0 Information number 21, test mode is active
22_SETCH BOOLEAN 0 Information number 22, setting changed
Table continues on next page
Section 4 1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
34 670 series 2.2 IEC
Communication protocol manual