4.2.2 IED commands for IEC 60870-5-103 I103IEDCMD
4.2.2.1 Functionality
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5
I103IEDCMD is a command block in control direction with defined IED functions.
All outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
4.2.2.2 Function block
GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1
IEC10000283 V1 EN-US
Figure 14: I103IEDCMD function block
4.2.2.3 Signals
PID-3788-INPUTSIGNALS v5
Table 32: I103IEDCMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of commands
PID-3788-OUTPUTSIGNALS v5
Table 33: I103IEDCMD Output signals
Name Type Description
19-LEDRS BOOLEAN Information number 19, reset LEDs
23-GRP1 BOOLEAN Information number 23, activate setting group 1
24-GRP2 BOOLEAN Information number 24, activate setting group 2
25-GRP3 BOOLEAN Information number 25, activate setting group 3
26-GRP4 BOOLEAN Information number 26, activate setting group 4
4.2.2.4 Settings
PID-3788-SETTINGS v5
Table 34: I103IEDCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 255 Function type (1-255)
Section 4 1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
42 670 series 2.2 IEC
Communication protocol manual