5.6 Modbus RTU
Modbus RTU communication configuration (Embedded System bus)
Set the address of the connected ITS module, 0~247 selectable, default
Set the baud rate of the connected ITS module,
9600, 19200 selectable, default 19200
Protocol type
Set the physical protocol
bit, 8 data bits, 1 STOP bit, default
1 ODD parity bit, 8 data bits, 1 STOP bit
No parity bit, 8 data bits, 2 STOP bi
No parity bit, 8 data bits, 1 STOP bit
Modbus communication statistics (Embedded System bus)
received
Number of messages received by Ekip connect from ITS
received with CRC error
Number of messages received by Ekip connect with CRC error from ITS
messages sent by Ekip connect to ITS
Exception
Number of messages sent by Ekip connect to ITS and received by ITS successfully
Exception: Slave Device
Busy
Number of messages sent by Ekip connect to ITS but not rec
eived by ITS because ITS busy