EasyManua.ls Logo

ABB ITS2.1 - Standalone ITS Multiplug

ABB ITS2.1
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ITS2.1 User Manual rev.04/1SEP622750P0001 24
6.2 Standalone ITS module multiplug
For OT&OS and other switches, ITS and adapter module is a standalone product which needs to be connected
to switch by external cable.
Multiplug to user side Terminal pins definition
Terminal
Signal
Cable
X1:1
24 VDC
power supply input
AWG22~16, 300/500V, Temp 125
X1:2
24 V GND (0V)
X1:3
RS
-
485 0V
Belden 3105A or equivalent
X1:4
RS
-
485 + (A)
X1:5
RS
-
485
(B)
Other signals Multiplug to
Switch side
Terminal pins definition
Terminal
Signal
C
able
X2:1
Temperature sensor
base
polar
ABB provides
X2:2
Not in use
-
X2:3
L3 Current sensing signal Negative
AWG18, 300/500V, Temp 125
X2:4
L2 Current sensing signal Negative
AWG18, 300/500V, Temp 125
X2:5
L1 Current sensing signal Negative
AWG18, 300/500V, Temp 125
X2:6
Switch position input signal Positive
AWG24, 300/500V, Temp 125
X2:7
Not in use
-
X2:8
Switch control common port
AWG24, 300/500V, Temp 125
X2:9
Temperature sensor
emitter
polar
ABB provides
X2:10
ITS GND(0V)
ABB
provides
X2:11
L3 Current sensing signal Positive
AWG18, 300/500V, Temp 125
X2:12
L2 Current sensing signal Positive
AWG18, 300/500V, Temp 125
X2:13
L1 Current sensing signal Positive
AWG18, 300/500V, Temp 125
X2:14
Switch position input
signal
negative
AWG24, 300/500V, Temp 125
X2:15
Switch open control signal output
AWG24, 300/500V, Temp 125
X2:16
Switch close control signal output
AWG24, 300/500V, Temp 125
Voltage Multiplug to
Switch side
Terminal pins definition
Terminal
Signal
Cable
X3:4
L3 voltage input
AWG20, 1000V Temp 200
X3:5
L2 voltage input
AWG20, 1000V Temp 200
X3:6
L1 voltage input
AWG20, 1000V Temp 200
1
8
9 16
1 2
3
4
5
6

Related product manuals