ITS2.1 User Manual rev.04/1SEP622750P0001 43
15 TROUBLE SHOOTING
Fault Description Fault Analysis Trouble shooting method
Detected current value cannot
match to actual current
Switch rated current may not be set
correctly
Check rated current setting on Ekip connect
Main page and correct it on ITS2
configuration page
Slimline/OTM/OSM cannot be
controlled to open/close by ITS
Switch type may be set as InlineII but
InlineII has no motor
Check switch type setting on Ekip connect
Main page and correct it on ITS2
configuration page
Fuse blown function cannot work This function wasn’t enabled Check Fuse blown handling setting on Ekip
connect Main page and correct it on ITS2
configuration page
Nominal line voltage wasn’t set correctly Check nominal line voltage setting on Ekip
connect Main page and correct it on ITS2
configuration page
No voltage data showed Feeding direction wasn’t set correctly on
switch
Check the feeding direction setting
according to Section 9