ITS2.1 User Manual rev.04/1SEP622750P0001 29
10 POWER DIRECTION SETTING
10.1 Slimline XRG power direction setting
Note:Relevant for XRG1,2 and 3 only, XRG00 is made for busbar feed only
This is done by placing straps on the Fuse boards located behind the fuses in correct position.
By default the straps are set in the position marked “Busbar Feed”.
Note: Make sure the feeding side setting in Ekip connect aligns to the power direction setting on slimline.
XRG1, 2 and 3 can be fed from the busbar side
(busbar feed) or from the cable terminal side
(terminal feed)
By default the straps are set in the position
marked “Busbar Feed” and the corresponding
feeding side in Ekip connect is BUSBAR SIDE.