ITS2.1 User Manual rev.04/1SEP622750P0001 25
7 MODBUS RTU
Default Modbus addr. 247
7.1 Special sequence Modbus telegram
The parameters presented in the Main Measures menu is available as one contiguous block in the Modbus
mapping, making it easy and time saving to read the most common parameters from the ITS2.1 unit.
The following parameters can be read:
7.2 Modbus RTU trouble and fault finding
There are several ways to troubleshoot a Modbus line.
Assuming the Modbus line is OK hardware vice: correct polarity, no similar addresses, trouble with
termination, reading of Modbus register issues etc., a laptop with USB – RS-485 converter and Ekip connect
can be used for testing the Modbus line. It will even handle multidrop.
Actual current measure by the CT’s
Calculated 3 phase active power (kW)
Calculated 3 phase reactive power (kvar)
Sum of positive and negative active energy (kWh)
Calculated 3 phase power factor
Actual temperature measure on
Switch status and Fuse blown status