Parameters 91
188.32 Underfrequency time 1 Sets trip time for underfrequency protection. 100 ms
0 ... 120 000 ms 1 = 1 ms
188.33 Underfrequency enable 2 Enables underfrequency protection. 1
0 ... 1 1 = 1
188.34 Underfrequency limit 2 Sets limit for underfrequency protection. -1 Hz
-30 ... 0 Hz 1 = 1 Hz /
10 = 1 Hz
188.35 Underfrequency time 2 Sets trip time for underfrequency protection. 100 ms
0 ... 120 000 ms 1 = 1 ms
188.40 Overfrequency enable 1 Enables overfrequency protection. 1
0 ... 1 1 = 1
188.41 Overfrequency limit 1 Sets limit for overfrequency protection. 1 Hz
0 ... 30 Hz 1 = 1 Hz /
10 = 1 Hz
188.42 Overfrequency time 1 Sets trip time for overfrequency protection. 100 ms
0 ... 120 000 ms 1 = 1 ms
188.43 Overfrequency enable 2 Enables overfrequency protection. 1
0 ... 1 1 = 1
188.44 Overfrequency limit 2 Sets limit for overfrequency protection. 1 Hz
0 ... 30 Hz 1 = 1 Hz /
10 = 1 Hz
188.45 Overfrequency time 2 Sets trip time for overfrequency protection. 100 ms
0 ... 120 000 ms 1 = 1 ms
188.50 Undervoltage enable 1 Enables undervoltage protection. 1
0 ... 1 1 = 1
188.51 Undervoltage limit 1 Sets limit for undervoltage protection. 80
0 ... 100% 1 = 1
188.52 Undervoltage time 1 Sets trip time for undervoltage protection. 100 ms
0 ... 120 000 ms 1 = 1 ms
188.53 Undervoltage enable 2 Enables undervoltage protection. 0
0 ... 1 1 = 1
188.54 Undervoltage limit 2 Sets limit for undervoltage protection. 80%
0 ... 100% 1 = 1%
188.55 Undervoltage time 2 Sets trip time for undervoltage protection. 0 ms
0 ... 120 000 ms 1 = 1 ms
188.63 Overvoltage enable 1 Enables overvoltage protection. 1
0 ... 1 1 = 1
188.64 Overvoltage limit 1 Sets limit for overvoltage protection. 110
100 ... 200% 1 = 1
188.65 Overvoltage time 1 Sets trip time for overvoltage protection. 100 ms
0 ... 120 000 ms 1 = 1 ms
No. Name/Value/Range Description Default
FbEq (16b/32b)