92 Parameters
188.66 Overvoltage enable 2 Enables overvoltage protection. 0
0 ... 1 1 = 1
188.67 Overvoltage limit 2 Sets limit for overvoltage protection. 120
100 ... 200% 1 = 1
188.68 Overvoltage time 2 Sets trip time for overvoltage protection. 0 ms
0 ... 120 000 ms 1 = 1 ms
188.69 Overvoltage enable 3 Enables overvoltage protection. 0
0 ... 1 1 = 1
188.70 Overvoltage limit 3 Sets limit for overvoltage protection. 130
100 ... 200% 1 = 1
188.71 Overvoltage time 3 Sets trip time for overvoltage protection. 0 ms
0 ... 120 000 ms 1 = 1 ms
188.72 Sliding overvoltage enable Enables sliding overvoltage protection. 0
0 ... 1 1 = 1
188.73 Sliding overvoltage limit Sets limit for sliding overvoltage protection. 120%
100 ... 200% 1 = 1%
188.74 Sliding overvoltage time Sets trip time for sliding overvoltage protection. 100 ms
0 ... 60 000 ms 1 = 1 ms
188.80 Combinatory trip Enables combinatory protection. 0
0 ... 1 1 = 1
188.81 Combinatory trip time Sets trip time for combinatory protection. 100 ms
0 ... 60 000 ms 1 = 1 ms
188.84 Comb pos seq voltage limit Sets positive sequence voltage limit in percent of
nominal line-to-line AC voltage for combinatory
protection.
130%
0 ... 200% 1 = 1 %
188.85 Comb neg seq voltage limit Sets negative sequence voltage limit in percent of
nominal line-to-line AC voltage for combinatory
protection.
10%
0 ... 200% 1 = 1%
188.86 Comb underfrequency limit Sets limit for combinatory underfrequency
protection.
-5 Hz
-30 ... 0 Hz 1 = 1 Hz /
10 = 1 Hz
188.87 Comb overfrequency limit Sets limit for combinatory overfrequency
protection.
5 Hz
0 ... 30 Hz 1 = 1 Hz /
10 = 1 Hz
188.110 Rate of change of freq
enable
Enables rate of change of frequency limit. 0
0 ... 1 1 = 1
No. Name/Value/Range Description Default
FbEq (16b/32b)