Ex relevant specifications for operation in Div. 1
28 - EN FEX300, FEX500 SM/FEX300/FEX500/FM/CSA-EN
Table 4: Fluid temperature (Ex data) for HygienicMaster models FEH315, FEH515
Nominal diameter
Design
Temperature
class
Ambient temperature
(- 40 °C)
1)
- 20 °C ... + 40 °C (- 40 °C)
1)
- 20 °C ... + 50 °C (- 40 °C)
1)
- 20 °C ... + 60 °C
Not thermally
insulated
Thermally
insulated
Not thermally
insulated
Thermally
insulated
Not thermally
insulated
Thermally
insulated
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
DN 3 ... DN 100
NT
T1
130 °C 110 °C 20 °C 80 °C 40 °C
HT 180 °C 120 °C 20 °C 120 °C 20 °C
NT
T2
130 °C 110 °C 20 °C 80 °C 40 °C
HT 180 °C 120 °C 20 °C 120 °C 20 °C
NT
T3
130 °C 110 °C 20 °C 80 °C 40 °C
HT 180 °C 120 °C 20 °C 120 °C 20 °C
NT
T4
120 °C 110 °C 20 °C 80 °C 40 °C
HT 120 °C 120 °C 20 °C 120 °C 20 °C
NT
T5
85 °C 85 °C 20 °C 80 °C 40 °C
HT 85 °C 85 °C 20 °C 85 °C 20 °C
NT
T6
70 °C 70 °C 20 °C 70 °C 40 °C
HT 70 °C 70 °C 20 °C 70 °C 20 °C
1) Low-temperature version (option)
NT standard version, T
medium
maximum 130 °C (266 °F).
HT high temperature version, T
medium
maximum 180 °C (356 °F).
Not thermally insulated: The flowmeter sensor is not surrounded by pipe insulation material.
Thermally insulated: The flowmeter sensor is surrounded by pipe insulation material.
Note
The standard version includes explosion protection for gases and dust. Explosion protection for dust is only available for devices featuring a
transmitter in a dual-compartment housing.
If the installation location for the device is classified as a potentially explosive area for gases and dust, the temperature data in the "Gas &
dust" columns in the table must be taken into consideration.
If the installation location for the device is classified as a potentially explosive area for gases only, the temperature data in the "Gas" column
in the table must be taken into consideration.