8:1.3.2 Analog input telegram
To PLC from Softstarter. All analog data will be represented by 16 bit values.
Word in
input
data area
Binary
input
byte
Bit Data Description
2 Fault Line side Event Status
3 Spare (Value = 0)
4 Spare (Value = 0)
5 Spare (Value = 0)
6 Spare (Value = 0)
7 Spare (Value = 0)
5 8 (0) Spare (Value = 0)
9 (1) Spare (Value = 0)
10 (2) Spare (Value = 0)
11 (3) Spare (Value = 0)
12 (4) Spare (Value = 0)
13 (5) Spare (Value = 0)
14 (6) Spare (Value = 0)
15 (7) Spare (Value = 0)
Chapter 8 - Fieldbus communication (option)
Word in input
area
Analogue
input word
Data Representation
3 0 Phase current L1 Value =1000 » 1000A
4 1 Phase current L2 Value =1000 » 1000A
5 2 Phase current L3 Value =1000 » 1000A
6 3 Max phase current Value =1000 » 1000A
7 4 Measured frequency Value =100 » 100Hz
8 5 Output voltage Value =100 » 100%
9 6 Calc. Motor temp. Value =100 » 100%
10 7 Counted no of Starts Value =100 » 10000 times
11 8 Run Time Value =100 » 1000 hours