Low Voltage Products & Systems 135
ABB Inc. 888-385-1221 www.abb-control.com AC 1006.9 - 5/03
Chapter 10 - Functions
10:32 Phase reversal protection, type of op-
eration
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Phase Rev/Ph Rev Op
This parameter makes it possible to select between three different
actions when the protection is activated. It is active only if the phase
reversal protection is selected.
10:33 PTC protection
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/PTC
The softstarter has an input for an external PTC thermistor that can
be used independent of the built-in electronic overload protection
status.
Stop M
Stop A
Ind
The motor stops and an automatic reset
is performed when the fault disappears.
The motor continues to run but a fault
indication is given.
The motor stops and a manual reset is
required before restart.
Parameter
text
Default
value
Setting
range
Description
Ph Rev Op Stop-M
Stop-M,
Stop-A, Ind
Type of
operation for
phase
reversal
protection
Parameter
text
Default
value
Setting
range
Description
PTC No Yes, No
PTC
protection