126 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 10 - Functions
10:14 Overload class
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Overload/OL Class
This parameter makes it possible to set the required overload class.
Four different classes are available according to Figure 8.
• Class 10A
• Class 10
• Class 20
• Class 30
10:15 Overload class, dual type, start class
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Overload/Dual Class S
This parameter makes it possible to set the required overload class
during start. When full voltage is reached, there will be a switch-over
to run class (see below).
1
10
100
1000
1
23456
A
B
C
D
1SFC132102F0001
Time(s)
Current
(x I
e
)
Figure 8: Tripping curves for the
electronic overload
A Class 30
B Class 20
C Class 10
D Class 10A
Parameter
text
Default
value
Setting
range
Description
OL Class 10
10A, 10, 20,
30
Overload
class
Parameter
text
Default
value
Setting
range
Description
OL Class S 10
10A, 10, 20,
30
Overload
class