Chapter 5 - Connection
5:2.2 Control voltage and control circuit
5:2.2.1 Control voltage, terminals 1 and 2
Connect the hot and neutral and phase to terminals 1 and 2.
Check that you have the correct control voltage U
s
.
5:2.2.2 Grounding, terminal 3
Connect the cable to a grounding point close to the softstarter.
The cable should be as short as possible. A suitable grounding point
would be next to the softstarter on the mounting plate, see Figure 7.
The mounting plate should also be grounded.
This is not a protective ground, it is a functional ground. The
grounding cable should be as short as possible.
1
100-250V
Stop
Start
In0
In1
50/60 Hz
2
3
4
5
6
7
L
N
1SFC132051F0001
1
100-250V
Stop
Start
In0
In1
50/60 Hz
2
3
4
5
6
7
1SFC132052F0001
M3
1. . . . . . . . . . . . . . . . . . . . . . . . 20
0.5 Nm - 4.3 lb.in
3.5x0.6
0.14 ... 2.5 mm
AWG 12 ... 22
0.14 ... 2.5 mm
2
2
1SFC132053F0001
Figure 6: Control voltage
Figure 7: Functional ground
Figure 8: Tightening torques and cable sizes