EasyManua.ls Logo

ABB REB670 - Second Harmonic Restrain

ABB REB670
554 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HarmRestrainx: Enable block of step x from the harmonic restrain function (2nd
harmonic). This function should be used when there is a risk if power transformer
inrush currents might cause unwanted trip. Can be set Off/On.
tPCrvx, tACrvx, tBCrvx, tCCrvx: Parameters for customer creation of inverse time
characteristic curve (Curve type = 17). See equation 30 for the time characteristic
equation.
[ ]
>
p
A
t s B IxMult
i
C
in
= + ×
-
æ ö
ç ÷
ç ÷
ç ÷
æ ö
ç ÷
ç ÷
è ø
è ø
EQUATION1261 V2 EN-US (Equation 30)
For more information, please refer to the “Technical r
eference manual”.
tPRCrvx, tTRCrvx, tCRCrvx: Parameters for customer creation of inverse reset time
characteristic curve (Reset Curve type = 3). Further description can be found in the
Technical reference manual”.
7.2.3.2 Second harmonic restrain
SEMOD127941-90 v1
If a power transformer is energized there is a risk that the transformer core will saturate
during part of the period, resulting in an inrush transformer current. This will give a
declining residual current in the network, as the inrush current is deviating between the
phases. There is a risk that the phase overcurrent function will give an unwanted trip.
The inrush current has a relatively large ratio of 2
nd
harmonic component. This
component can be used to create a restrain signal to prevent this unwanted function.
The settings for the 2
nd
harmonic restrain are described below.
2ndHarmStab: The rate of second harmonic current content for activation of the 2
nd
harmonic restrain signal, to block chosen steps. The setting is given in % of the
fundamental frequency residual current. The setting range is 5-100% in step of 1%.
The default setting is 20%.
HarmRestrainx: This parameter can be set Off/On, disable or enable the 2
nd
harmonic
restrain.
The four-step phase overcurrent protection can be used in different ways, depending on
the application where the protection is used. A general description is given below.
The pick up current setting inverse time protection or the lowest current step constant
inverse time protection must be given a current setting so that the highest possible load
1MRK 505 370-UUS A Section 7
Current protection
Busbar protection REB670 2.2 ANSI 191
Application manual

Table of Contents

Other manuals for ABB REB670

Related product manuals