ABB REB670 - Examples on How to Connect a Three Phase-To-Ground Connected VT to the IED

ABB REB670
554 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
100 V
1
10 V
115 V
120 V
230 V
The IED fully supports all of these values and most of them will be shown in the
following examples.
4.2.4.3 Examples on how to connect a three phase-to-ground connected VT to
the IED
SEMOD55055-87 v9
Figure
28 gives an example on how to connect the three phase-to-ground
connected
VT to the IED. It gives an overview of required actions by the user in order to make
this measurement available to the built-in protection and control functions within the
IED.
For correct terminal designations, see the connection diagrams valid for
the delivered IED.
Section 4 1MRK 505 370-UUS A
Analog inputs
86 Busbar protection REB670 2.2 ANSI
Application manual