EasyManua.ls Logo

ABB REB670 - Interlocking for Line Bay ABC_LINE (3); Application; Signals from Bypass Busbar

ABB REB670
554 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
when they are set to 0=FALSE.
12.4.2 Interlocking for line bay ABC_LINE
(3)
IP14139-1 v2
12.4.2.1 Application
M13561-3 v8
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure
141. The
function can also be used for a double busbar arrangement without transfer busbar or a
single busbar arrangement with/without transfer busbar.
189
289
189G
289G
989
989G
WA1 (A)
WA2 (B)
WA7 (C)
789
en04000478_ansi.vsd
152
ANSI04000478 V1 EN-US
Figure 141: Switchyard layout ABC_LINE (3)
M13560-4 v5
The signals from other bays connected to the module ABC_LINE (3) are described
below.
12.4.2.2 Signals from bypass busbar
M13560-6 v5
To derive the signals:
Signal
BB7_D_OP All line disconnectors on bypass WA7 except in the own bay are open.
VP_BB7_D The switch status of disconnectors on bypass busbar WA7 are valid.
EXDU_BPB No transmission error from any bay containing disconnectors on bypass busbar
WA7
1MRK 505 370-UUS A Section 12
Control
Busbar protection REB670 2.2 ANSI 363
Application manual

Table of Contents

Other manuals for ABB REB670

Related product manuals