EasyManua.ls Logo

ABB REB670 - Signals from Bus-Coupler

ABB REB670
554 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
These signals from each line bay (ABC_LINE, 3) except that of the own bay are
needed:
Signal
789OPTR 789 is open
VP789TR The switch status for 789 is valid.
EXDU_BPB No transmission error from the bay that contains the above information.
For bay n, these conditions are valid:
AND
BB7_D_OP
VP_BB7_D
EXDU_BPB
en04000477_ansi.vsd
AND
AND
789OPTR (bay 1)
789OPTR (bay 2)
. . .
. . .
789OPTR (bay n-1)
VP789TR (bay 1)
VP789TR (bay 2)
. . .
. . .
VP789TR (bay n-1)
EXDU_BPB (bay 1)
EXDU_BPB (bay 2)
. . .
. . .
EXDU_BPB (bay n-1)
ANSI04000477 V1 EN-US
Figure 142: Signals from bypass busbar in line bay n
12.4.2.3 Signals from bus-coupler
M13560-31 v4
If the busbar is divided by bus-section disconnectors into bus sections, the busbar-
busbar connection could exist via the bus-section disconnector and bus-coupler within
the other bus section.
Section 12 1MRK 505 370-UUS A
Control
364 Busbar protection REB670 2.2 ANSI
Application manual

Table of Contents

Other manuals for ABB REB670

Related product manuals