13.12.2 Application
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
The function TEIGAPC is used for user-defined logics and it can also be used for
dif
ferent purposes internally in the IED. An application example is the integration of
elapsed time during the measurement of neutral point voltage or neutral current at
earth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed to 999999.9 seconds.
13.12.3 Setting guidelines
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
The settings tAlarm and tWarning are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm99 999.99 seconds
1.00 second ≤ tWarning99 999.99 seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit float
representation
99 999.99 seconds < tAlarm999 999.0 seconds
99 999.99 seconds < tWarning999 999.0 seconds
Note that tAlarm and tWarning
are independent settings, that is, there is
no check if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 999999.9 seconds.
13.13 Comparator for integer inputs - INTCOMP
13.13.1
Identification
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparison of integer values INTCOMP Int<=>
1MRK 505 370-UUS A Section 13
Logic
Busbar protection REB670 2.2 ANSI 421
Application manual