IEC16000038-1-en.vsd x
AP1
PhyPortB
PhyPortA
AP1
PhyPortA
PhyPortB
AP1
PhyPortA
PhyPortB
AP1
PhyPortB
PhyPortA
Device 1 Device 2
Device 3
Device 4
IEC16000038 V1 EN-US
Figure 198: High-availability Seamless Redundancy (HSR)
16.2.3 Setting guidelines
GUID-887B0AE2-0F2E-414D-96FD-7EC935C5D2D8 v1
Redundant communication is configured with the Ethernet configuration tool in
PCM600.
Redundancy: redundant communication is activated when the parameter is set to
PRP-0, PRP-1 or HSR. The settings for the next access point will be hidden and
PhyPortB will show the second port information. Redundant communication is
activated after a common write to IED is done.
PRP-1 should be used primarily, PRP-0 is intended only for use in existing PRP-
networks. PRP-1 and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet
Configuration Tool can be used to activate the access point.
1MRK 505 370-UUS A Section 16
Ethernet-based communication
Busbar protection REB670 2.2 ANSI 469
Application manual