Figure 179: Switchyard layout breaker-and-a-half
M13570-7 v4
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and
BH_LINE_B (3) are the connections from a line to a busbar. BH_CONN (3) is the
connection between the two lines of the diameter in the breaker-and-a-half switchyard
layout.
M13569-4 v4
For a breaker-and-a-half arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.
12.4.9.2 Configuration setting
M13569-6 v5
For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
• 989_OP = 1
• 989_CL = 0
• 989G_OP = 1
• 989G_CL = 0
1MRK 505 370-UUS A Section 12
Control
Busbar protection REB670 2.2 ANSI 397
Application manual