ACTIVE
Indicates that the auto recloser is active, from start until end of reset time
.
BLOCKED
Indicates that auto recloser is temporarily or permanently blocked.
CLOSECMD
Connect to a binary output for circuit breaker closing command.
COUNT1P, COUNT2P, COUNT3P1, COUNT3P2, COUNT3P3,
COUNT3P4 and COUNT3P5
Indicates the number of auto reclosing shots made for respective shot.
COUNTAR
Indicates the total number of auto reclosing shots made.
INHIBOUT
If the INHIBIT input is activated it is reported on the INHIBOUT output.
INPROGR
Indicates that an auto recloser sequence is in progress, from start until circuit breaker
close command.
MODE
When a valid integer is connected to the MODEINT input, the selected ARMode setting
will be invalid and the MODEINT input value will be used instead. The selected mode
is reported as an integer on the MODE output. The six possible modes are described in
Table
38 with their corresponding MODEINT integer value.
PERMIT1P
Permit single-pole trip is the inverse of PREP3P. It can be connected to a binary output
relay for connection to external protection or trip relays. In case of a total loss of
auxiliary power
, the output relay drops and does not allow single-pole trip.
PREP3P
Prepare three-pole trip is usually connected to the trip block to force a coming trip to
be a three-pole one. If the auto recloser cannot make a single-pole or two-pole auto
reclosing, the tripping should be three-pole.
1MRK 505 370-UUS A Section 12
Control
Busbar protection REB670 2.2 ANSI 331
Application manual