Name Type Default Description
PRES_ALM_IN BOOLEAN 0=False Binary pressure alarm input
PRES_LO_IN BOOLEAN 0=False Binary pressure input for lockout indication
SPR_CHR_ST BOOLEAN 0=False CB spring charging started input
SPR_CHR BOOLEAN 0=False CB spring charged input
RST_IPOW BOOLEAN 0=False Reset accumulation energy
RST_CB_WEAR BOOLEAN 0=False Reset input for CB remaining life and operation
counter
RST_TRV_T BOOLEAN 0=False Reset input for CB closing and opening travel times
RST_SPR_T BOOLEAN 0=False Reset input for the charging time of the CB spring
Table 526: SSCBR Output signals
Name Type Description
TRV_T_OP_ALM BOOLEAN CB open travel time exceeded set value
TRV_T_CL_ALM BOOLEAN CB close travel time exceeded set value
SPR_CHR_ALM BOOLEAN Spring charging time has crossed the set value
OPR_ALM BOOLEAN Number of CB operations exceeds alarm limit
OPR_LO BOOLEAN Number of CB operations exceeds lockout limit
IPOW_ALM BOOLEAN Accumulated currents power (Iyt),exceeded alarm
limit
IPOW_LO BOOLEAN Accumulated currents power (Iyt),exceeded
lockout limit
CB_LIFE_ALM BOOLEAN Remaining life of CB exceeded alarm limit
MON_ALM BOOLEAN CB 'not operated for long time' alarm
PRES_ALM BOOLEAN Pressure below alarm level
PRES_LO BOOLEAN Pressure below lockout level
OPENPOS BOOLEAN CB is in open position
INVALIDPOS BOOLEAN CB is in invalid position (not positively open or
closed)
CLOSEPOS BOOLEAN CB is in closed position
7.1.7  Settings
Table 527: SSCBR Non group settings
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
    1=on Operation Off / On
Acc stop current 5.00...500.00 A 0.01 10.00 RMS current setting below which engy
acm stops
Open alarm time 0...200 ms 1 40 Alarm level setting for open travel time in
ms
Close alarm time 0...200 ms 1 40 Alarm level Setting for close travel time
in ms
Table continues on next page
Section 7 1YHT530004D05 D
Condition monitoring functions
620 615 series
Technical Manual