16.4.5 Settings
PID-3267-SETTINGS v9
Table 766: SSCBR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
PhSel Phase A
Phase B
Phase C
- - Phase A Phase selection
RatedOperCurr 100.00 - 5000.00 A 0.01 1000.00 Rated operating current of the breaker
OperNoRated 1 - 99999 - 1 10000 Number of operations possible at rated
current
RatedFltCurr 500.00 - 99999.99 A 0.01 5000.00 Rated fault current of the breaker
OperNoFault 1 - 10000 - 1 1000 Number of operations possible at rated
fault current
tTrOpenAlm 0.000 - 0.200 s 0.001 0.040 Alarm level for open travel time
tTrCloseAlm 0.000 - 0.200 s 0.001 0.040 Alarm level for close travel time
OperAlmLevel 0 - 9999 - 1 200 Alarm level for number of operations
OperLOLevel 0 - 9999 - 1 300 Lockout level for number of operations
AccSelCal Aux Contact
Trip Signal
- - Trip Signal Accumulated energy calculation selection
CurrExponent 0.50 - 3.00 - 0.01 2.00 Current exponent value used for energy
calculation
AccStopCurr 5.00 - 100.00 %IB 0.01 10.00 RMS current level below which energy
accumulation stops
AlmAccCurrPwr 0.00 - 20000.00 - 0.01 2500.00 Alarm level for accumulated
I^CurrExponent integrated over CB open
travel time
LOAccCurrPwr 0.00 - 20000.00 - 0.01 2500.00 Lockout level for accumulated
I^CurrExponent integrated over CB open
travel time
SpChAlmTime 0.00 - 60.00 s 0.01 1.00 Alarm level for spring charging time
InitCBRemLife 1 - 99999 - 1 10000 Initial value for remaining life estimates
InactiveAlDays 0 - 9999 Day 1 2000 Alarm level for inactive days counter
Table 767: SSCBR Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
OpenTimeCorr -0.100 - 0.100 s 0.001 0.010 Correction for open travel time
CloseTimeCorr -0.100 - 0.100 s 0.001 0.010 Correction for close travel time
DirCoef -3.00 - -0.50 - 0.01 -1.50 Directional coefficient for CB life
calculation
CBLifeAlmLevel 1 - 99999 - 1 5000 Alarm level for CB remaining life
Table continues on next page
Section 16 1MRK 502 066-UUS B
Monitoring
1050
Technical manual