EasyManua.ls Logo

ABB Relion 670 series - Open CT Detection Feature

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.3.7.5 Open CT detection feature
GUID-BBA6C2DD-50A2-437C-8535-D61B68F3FAE4 v1
Transformer differential protection has a built-in, advanced open CT detection feature.
A sudden inadvertently opened CT circuit may cause an unexpected and unwanted operation of
the Transformer differential protection under normal load conditions. Damage of secondary
equipment may occur due to high voltage from open CT circuit outputs. It is always an advantage,
from the point of view of security and reliability, to have the open CT detection function to block
the transformer differential protection function in case of an open CT condition, and produce an
alarm signal to the operational personnel to quickly correct the open CT condition.
The built-in open CT feature can be enabled or disabled by the setting parameter
OpenCTEnable
(
Disabled
/
Enabled
). When enabled, this feature tries to prevent mal-operation when a loaded main
CT connected to Transformer differential protection is by mistake open circuited on the secondary
side. Note that this feature can only detect interruption of one CT phase current at a time. If two
or even all three-phase currents of one set of CTs are accidentally interrupted at precisely the
same time, this feature cannot operate. Transformer differential protection generates a trip signal
if the false differential current is sufficiently high. An open CT circuit is typically detected in 12–14
ms, and if the load in the protected circuit is relatively high, about the nominal load, the unwanted
trip cannot always be prevented. Still, the information about what was the cause of the open CT
secondary circuit, is vital.
The principle applied to detect an open CT is a simple pattern recognition method, similar to the
waveform check used by the Power transformer differential protection in order to detect the
magnetizing inrush condition. The open CT detection principle is based on the fact that for an
open CT, the current in the phase with the open CT suddenly drops to zero (that is, as seen by the
protection), while the currents of the other two phases continue as before.
The open CT function is supposed to detect an open CT under normal conditions, that is, with the
protected multi-terminal circuit under normal load (10...110% of the rated load). If the load
currents are very low or zero, the open CT condition cannot be detected. In addition to load
condition requirement, Open CT function also checks the differential current on faulty phase. If the
differential current is lower than 50% of IdMin, the open CT condition cannot be detected.
Therefore, the Open CT algorithm only detects an open CT if the load on the power transformer is
10...110% of rated load and the differential current is higher than 50% of IdMin on that phase. The
search for an open CT starts 60 seconds (50 seconds in 60 Hz systems) after the transformer is
energized. The Open CT detection feature can also be explicitly deactivated by setting:
OpenCTEnable
= 0 (
Disabled
).
If an open CT is detected and the output OPENCT set to 1, then all the differential functions are
blocked, except the unrestrained (instantaneous) differential. An alarm signal is also produced
after a settable delay (
tOCTAlarmDelay
) to report to operational personnel for quick remedy
actions once the open CT is detected. When the open CT condition is removed (that is, the
previously open CT is reconnected), the functions remain blocked for a specified interval of time,
which is also defined by a setting (
tOCTResetDelay
). This is to prevent an eventual mal-operation
after the reconnection of the previously open CT secondary circuit.
The open CT algorithm provides detailed information about the location of the defective CT
secondary circuit. The algorithm clearly indicates the IED side, CT input and phase in which an
open CT condition has been detected. These indications are provided via the following outputs
from the Transformer differential protection function:
1MRK 502 066-UUS B Section 6
Differential protection
161
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals