13.2.8 Technical data
M16069-1 v11
Table 432: FUFSPVCtechnical data
Function Range or value Accuracy
Trip voltage, zero sequence (1-100)% of VBase ±0.5% of V
n
Trip current, zero sequence (1–100)% of IBase ±0.5% of I
n
Trip voltage, negative sequence (1-100)% of VBase ±0.5% of V
n
Trip current, negative sequence (1–100)% of IBase ±0.5% of I
n
Trip voltage change pickup (1-100)% of VBase ±10.0% of V
n
Trip current change pickup (1–100)% of IBase ±10.0% of I
n
Trip phase voltage (1-100)% of VBase ±0.5% of V
n
Trip phase current (1–100)% of IBase ±0.5% of I
n
Trip phase dead line voltage (1-100)% of VBase ±0.5% of V
n
Trip phase dead line current (1–100)% of IBase ±0.5% of I
n
Pickup time, 1 ph, pickup at 1 to 0 x V
n
Min. = 10 ms
Max. = 25 ms
-
Reset time, 1 ph, pickup at 0 to 1 x V
n
Min. = 15 ms
Max. = 30 ms
-
13.3 Fuse failure supervision VDSPVC (60)
GUID-9C5BA1A7-DF2F-49D4-A13A-C6B483DDFCDC v2
13.3.1 Identification
GUID-109434B0-23E5-4053-9E6E-418530A07F9C v2
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision VDSPVC VTS 60
13.3.2 Functionality
GUID-6AF2219A-264F-4971-8D03-3B8A9D0CB284 v4
Different protection functions within the protection IED operates on the basis of measured
voltage at the relay point. Some example of protection functions are:
• Distance protection function.
• Undervoltage function.
• Energisation function and voltage check for the weak infeed logic.
These functions can operate unintentionally, if a fault occurs in the secondary circuits between
voltage instrument transformers and the IED. These unintentional operations can be prevented by
VDSPVC.
Section 13 1MRK 502 066-UUS B
Secondary system supervision
742
Technical manual