Section 5 Local Human-Machine-Interface LHMI
5.1 Local HMI screen behaviour
5.1.1 Identification
GUID-84392EFF-4D3F-4A67-A6ED-34C6E98574D6 v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local HMI screen behaviour SCREEN - -
5.1.2 Settings
PID-6457-SETTINGS v3
Table 33: SCREEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
DisplayTimeout 1 - 120 Min 1 10 Local HMI display timeout
ContrastLevel -100 - 100 % 10 0 Contrast level for display
DefaultScreen - 0 Default screen
EvListSrtOrder Latest on top
Oldest on top
- - Latest on top Sort order of event list
AutoIndicationDRP Disabled
Enabled
- - Disabled Automatic indication of disturbance report
SubstIndSLD No
Yes
- - No Substitute indication on single line
diagram
InterlockIndSLD No
Yes
- - No Interlock indication on single line diagram
BypassCommands No
Yes
- - No Enable bypass of commands
5.2 Local HMI signals
5.2.1 Identification
GUID-03AB7AEE-87D3-4F3C-B6B9-B1EB1B538E38 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local HMI signals LHMICTRL - -
1MRK 502 066-UUS B Section 5
Local Human-Machine-Interface LHMI
83
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals