ABB Relion 670 series - Three-Phase Faults

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
0 max
100
3
INBlockPP
IphI < ×
EQUATION2110-ANSI V1 EN-US (Equation 52)
where:
IMinPUPG
is the minimum operation current for ground measuring loops,
3I0BLK_PP
is 3I
0
limit for blocking phase-to-phase measuring loop and
Iphmax is maximal magnitude of the phase currents.
7.2.6.3 Three-phase faults
M13140-80 v4
The operation conditions for three-phase faults are the same as for phase-to-phase fault, that is
equation , equation and equation are used to release the operation of the function.
However, the reach is expanded by a factor 2/√3 (approximately 1.1547) in all directions. At the
same time the characteristic is rotated 30 degrees, counter-clockwise. The characteristic is shown
in figure
85.
0.5·RFltFwdPP·K3
X1·K3
90 deg
0.5·RFltRevPP·K3
30 deg
R (ohm/phase)
X (ohm/phase)
4 X1
3
×
2 RFltFwdPP
3
×
ANSI05000671-4-en.vsd
2
K3
3
=
ANSI05000671 V4 EN-US
Figure 85: The characteristic of FDPSPDIS (21) for three-phase fault (setting parameters in
italic)
1MRK 502 066-UUS B Section 7
Impedance protection
205
Technical manual