5.3.4 Settings
PID-4114-SETTINGS v5
Table 39: LEDGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Operation Disabled/Enabled
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
t_MaxTripDelay 0.1 - 100.0 s 0.1 1.0 Maximum time for the definition of a
disturbance
PID-1697-SETTINGS v16
Table 40: GRP1_LED1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
SequenceType Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 1, local HMI alarm
group 1
LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm
group 1 is off
LabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm
group 1 is red
LabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm
group 1 is green
5.4 LCD part for HMI function keys control module
GUID-EECAE7FA-7078-472C-A429-F7607DB884EB v2
5.4.1 Identification
GUID-E6611022-5EA3-420D-ADCD-9D1E7604EFEB v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
LCD part for HMI Function Keys
Control module
FNKEYMD1 -
FNKEYMD5
- -
5.4.2 Function block
GUID-A803A728-5CFC-4606-98E4-793E873B99D4 v3
FNKEYMD1
^LEDCTL1 ^FKEYOUT1
IEC09000327 V1 EN-US
Figure 9: FNKEYMD1 function block
Section 5 1MRK 502 066-UUS B
Local Human-Machine-Interface LHMI
86
Technical manual