Name Type Default Description
I3PDIR GROUP
SIGNAL
- Group connection for directional current
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLK1 BOOLEAN 0 Block of step 1 (Pickup and trip)
BLK2 BOOLEAN 0 Block of step 2 (Pickup and trip)
BLK3 BOOLEAN 0 Block of step 3 (Pickup and trip)
BLK4 BOOLEAN 0 Block of step 4 (Pickup and trip)
MULTPU1 BOOLEAN 0 When activated, the pickup multiplier is in use for step1
MULTPU2 BOOLEAN 0 When activated, the pickup multiplier is in use for step2
MULTPU3 BOOLEAN 0 When activated, the pickup multiplier is in use for step3
MULTPU4 BOOLEAN 0 When activated, the pickup multiplier is in use for step4
52a BOOLEAN 0 Breaker position
CLOSECMD BOOLEAN 0 Breaker close command
OPENCMD BOOLEAN 0 Breaker open command
PID-6529-OUTPUTSIGNALS v4
Table 228: EF4PTOC (51N_67N) Output signals
Name Type Description
TRIP BOOLEAN General trip signal
TRST1 BOOLEAN Trip signal from step 1
TRST2 BOOLEAN Trip signal from step 2
TRST3 BOOLEAN Trip signal from step 3
TRST4 BOOLEAN Trip signal from step 4
TRSOTF BOOLEAN Trip signal from switch onto fault function
PICKUP BOOLEAN Common pickup signal
PUST1 BOOLEAN Pickup signal step 1
PUST2 BOOLEAN Pickup signal step 2
PUST3 BOOLEAN Pickup signal step 3
PUST4 BOOLEAN Pickup signal step 4
PUSOTF BOOLEAN Pickup signal from switch onto fault function
PUFW BOOLEAN Pick up foward direction
PUREV BOOLEAN Pick up reverse direction
2NDHARMD BOOLEAN 2nd harmonic block signal
8.4.5 Settings
IP11454-1 v2
Section 8 1MRK 502 066-UUS B
Current protection
472
Technical manual