17.1.4 Signals
PID-3830-INPUTSIGNALS v1
Table 798: PCFCNT Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
READ_VAL BOOLEAN 0 Initiates an additional pulse counter reading
BI_PULSE BOOLEAN 0 Connect binary input channel for metering
RS_CNT BOOLEAN 0 Resets pulse counter value
PID-3830-OUTPUTSIGNALS v1
Table 799: PCFCNT Output signals
Name Type Description
INVALID BOOLEAN The pulse counter value is invalid
RESTART BOOLEAN The reported value does not comprise a complete integration
cycle
BLOCKED BOOLEAN The pulse counter function is blocked
NEW_VAL BOOLEAN A new pulse counter value is generated
SCAL_VAL REAL Scaled value with time and status information
17.1.5 Settings
PID-3830-SETTINGS v1
Table 800: PCFCNT Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
EventMask NoEvents
ReportEvents
- - NoEvents Report mask for analog events from pulse
counter
CountCriteria Disabled
RisingEdge
Falling edge
OnChange
- - RisingEdge Pulse counter criteria
Scale 1.000 -
90000.000
- 0.001 1.000 Scaling value for SCAL_VAL output to unit
per counted value
Quantity Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
- - Count Measured quantity for SCAL_VAL output
tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter value
Section 17 1MRK 502 066-UUS B
Metering
1102
Technical manual