EasyManua.ls Logo

ABB Relion 670 series - Page 1290

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 current channels and 6 voltage channels
7 current channels and 5 voltage channels
9 current channels and 3 voltage channels
12 current channels
6 current channels
10 current channels and 2 voltage channels
TRM variants are available depending on the product. The rated values and channel type,
measurement or protection, of the current inputs are selected at order.
Transformer input module for measuring should not be used with current
transformers intended for protection purposes, due to limitations in overload
characteristics.
The TRM is connected to the ADM and NUM.
For configuration of the input and output signals, refer to section
"Signal matrix for analog inputs
SMAI".
ANSI08000479 V1 EN-US
Figure 647: TRM connection diagram
Section 22 1MRK 502 066-UUS B