22.5.5 Type tests according to standard
IP16288-1 v1
M16706-1 v13.1.1
Table 1057:Electromagnetic compatibility
Test Type test values Reference standards
1 MHz Oscillatory burst disturbance 2.5 kV IEC 60255-26
100 kHz slow damped oscillatory wave
immunity test
2.5 kV IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Surge withstand capability test 2.5 kV, oscillatory
4.0 kV, fast transient
IEEE/ANSI C37.90.1
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEC 60255-26
IEC 61000-4-2, Class IV
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.1
Fast transient disturbance 4 kV
2 kV, MIM mA-inputs
IEC 60255-26, Zone A
IEC 60255-26, Zone B
Surge immunity test
2-4 kV, 1.2/50ms high energy
1-2 kV, BOM and IRF outputs
IEC 60255-26, Zone A
IEC 60255-26, Zone B
Power frequency immunity test 150-300 V IEC 60255-26, Zone A
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s
100 A/m, cont.
IEC 61000-4-8, Class V
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Class V
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
Radiated electromagnetic field
disturbance
20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-26
Radiated electromagnetic field
disturbance
20 V/m
80-1000 MHz
10 V/m, 5.1-6.0 GHz
IEEE/ANSI C37.90.2
EN 50121-5
Conducted electromagnetic field
disturbance
10 V, 0.15-80 MHz IEC 60255-26
Radiated emission 30-5000 MHz IEC 60255-26
Radiated emission 30-5000 MHz IEEE/ANSI C63.4, FCC
Conducted emission 0.15-30 MHz IEC 60255-26
Table
1058:
Insulation
Test
Type test values Reference standard
Dielectric test 2.0 kV AC, 1 min.
1.0 kVrms, 1 min.)
IEC 60255-27
ANSI C37.90
IEEE 802.3-2015,
Environment A
Impulse voltage test
5 kV, 1.2/50ms, 0.5 J
1 kV, 1.2/50 ms 0.5 J
Insulation resistance
> 100 MW at 500 VDC
Section 22 1MRK 502 066-UUS B
IED hardware
1354
Technical manual