7.8.4 Signals
PID-6564-INPUTSIGNALS v2
Table 140: ZMFPDIS (21) Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Group signal for current input
V3P GROUP
SIGNAL
- Group signal for voltage input
BLOCK BOOLEAN 0 Blocks and resets timers and outputs of entire function
LOVBZ BOOLEAN 0 Blocks and resets timers and outputs of entire function
BLKZ1 BOOLEAN 0 Blocks and resets zone 1 timers and outputs
BLKZ2 BOOLEAN 0 Blocks and resets zone 2 timers and outputs
BLKZ3 BOOLEAN 0 Blocks and resets zone 3 timers and outputs
BLKZ4 BOOLEAN 0 Blocks and resets zone 4 timers and outputs
BLKZ5 BOOLEAN 0 Blocks and resets zone 5 timers and outputs
BLKZRV BOOLEAN 0 Blocks and resets reverse zone timers and outputs
BLKTRZ1 BOOLEAN 0 Blocks and resets zone 1 timers and trip outputs
BLKTRZ2 BOOLEAN 0 Blocks and resets zone 2 timers and trip outputs
BLKTRZ3 BOOLEAN 0 Blocks and resets zone 3 timers and trip outputs
BLKTRZ4 BOOLEAN 0 Blocks and resets zone 4 timers and trip outputs
BLKTRZ5 BOOLEAN 0 Blocks and resets zone 5 timers and trip outputs
BLKTRZRV BOOLEAN 0 Blocks and resets reverse zone timers and trip outputs
PID-6564-OUTPUTSIGNALS v2
Table 141: ZMFPDIS (21) Output signals
Name Type Description
TRIP BOOLEAN Trip in any phase or phases from any zone or zones
TRZ1 BOOLEAN Trip in any phase or phases from zone 1 - forward direction
TR_A_Z1 BOOLEAN Trip in phase A from zone 1 foward direction
TR_B_Z1 BOOLEAN Trip in phase B from zone 1 forward direction
TR_C_Z1 BOOLEAN Trip in phase C from zone 1 forward direction
TRZ2 BOOLEAN Trip in any phase or phases from zone 2 - forward direction
TR_A_Z2 BOOLEAN Trip in phase A from a zone 2 forward direction
TR_B_Z2 BOOLEAN Trip in phase B from zone 2 forward direction
TR_C_Z2 BOOLEAN Trip in phase C from zone 2 forward direction
TRZ3 BOOLEAN Trip in any phase or phases from zone 3 - zone direction
TRZ4 BOOLEAN Trip in any phase or phases from zone 4 - zone direction
TRZ5 BOOLEAN Trip in any phase or phases from zone 5 - zone direction
TRZRV BOOLEAN Trip in any phase or phases from zone RV - reverse dir.
BFI_3P BOOLEAN Pickup in any phase or phases from any zone or zones
Table continues on next page
Section 7 1MRK 502 066-UUS B
Impedance protection
294