7.8.5 Settings
PID-6564-SETTINGS v2
Table 142: ZMFPDIS (21) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable operation of the function
RLdFwd 0.01 - 5000.00 Ohm/p 0.01 60.00 Resistance determining the load
impedance area - forward
RLdRvFactor 1 - 1000 %RLdF
w
1 100 Resistance factor determining the load
impedance area - reverse
XLd 0.01 - 10000.00 Ohm/p 0.01 400.00 Resistance determining the load
impedance area - forward
LdAngle 5 - 70 Deg 1 30 Angle determining the load impedance
area
CVTType Any
Passive type
None (Magnetic)
- - Passive type CVT selection determining filtering of the
function
OpModePPZ1 Disabled
Quadrilateral
Mho
MhoOffset
- - Quadrilateral Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 1
OpModePGZ1 Disabled
Quadrilateral
Mho
MhoOffset
- - Quadrilateral Enabled/Disabled and characteristic
setting for Ph-G loops, zone 1
X1PPZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-Ph,
zone 1
R1PPZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-Ph,
zone 1
X1PGZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 positive sequence reactance reach, Ph-G,
zone 1
R1PZG1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-G,
zone 1
X0Z1 0.01 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, zone 1
R0Z1 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, zone 1
RFPPZ1 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 1
RFPGZ1 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-G, zone 1
tPPZ1 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Phase, zone 1
tPGZ1 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Ground-Earth, zone 1
IMinOpPPZ1 10 - 6000 %IB 1 10 Minimum operate ph-ph current for Phase-
Phase loops, zone 1
IMinOpPGZ1 5 - 6000 %IB 1 10 minimum operate phase current for phase-
ground loops. zone 1
OpModePPZ2 Disabled
Quadrilateral
Mho
MhoOffset
- - Quadrilateral Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 2