Figure 152: Fault loop model
Mho characteristic
GUID-9269239B-3A04-44CD-BE00-FD850D42836B v2
ZMFPDIS implements quadrilateral and mho characteristic in all the six zones separately. Set
OpModePEZx
or
OpModePPZx
setting to
Mho
or
Offset
, to choose a particular measuring loop in a
zone to work as mho (or Offset Mho) distance protection.
Zones 3 to 5 can be selected to be either forward or reverse with positive sequence polarized mho
characteristic; alternatively self polarized offset mho characteristics. The operating characteristic
is in accordance to figure
153 where zone 5 is selected offset mho.
Section 7 1MRK 502 066-UUS B
Impedance protection
308
Technical manual