7.9.5 Settings
PID-6488-SETTINGS v2
Table 150: ZMFCPDIS (21) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable operation of the function
OperationSC NoSeriesComp
SeriesComp
- - NoSeriesComp Selection of series compensation
operation Off / On
RLdFwd 0.01 - 5000.00 Ohm/p 0.01 60.00 Resistance determining the load
impedance area - forward
RLdRvFactor 1 - 1000 %RLdF
w
1 100 Resistance factor determining the load
impedance area - reverse
XLd 0.01 - 10000.00 Ohm/p 0.01 400.00 Resistance determining the load
impedance area - forward
LdAngle 5 - 70 Deg 1 30 Angle determining the load impedance
area
CVTType Any
Passive type
None (Magnetic)
- - Passive type CVT selection determining the filtering of
the function
OpModePPZ1 Disabled
Quadrilateral
Mho
MhoOffset
- - Quadrilateral Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 1
OpModePGZ1 Disabled
Quadrilateral
Mho
MhoOffset
- - Quadrilateral Enabled/Disabled and characteristic
setting for Ph-G loops, zone 1
X1FwPPZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive seq. reactance reach, Ph-Ph, zone
1, forward dir.
R1FwPPZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistive reach, Ph-Ph, zone 1,
forward dir.
X1RvPPZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Pos. seq. react. reach, Ph-Ph, zone 1,
reverse direction
X1FwPGZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive seq. reactance reach, Ph-G, zone 1,
forward dir.
R1FwPGZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistive reach, Ph-G, zone 1,
forward dir.
X0FwPGZ1 0.01 - 9000.00 Ohm/p 0.01 100.00 Zero seq. reactance reach, Ph-G, zone 1,
forward direction
R0FwPGZ1 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistive reach, Ph-G, zone 1,
forward direction
X1RvPgZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Pos. seq. react. reach, Ph-G, zone 1, reverse
direction
RFPPZ1 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 1
RFPGZ1 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-G, zone 1
tPPZ1 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Phase, zone 1
tPGZ1 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Ground-Earth, zone 1
Table continues on next page
1MRK 502 066-UUS B Section 7
Impedance protection
333
Technical manual