Name Values (Range) Unit Step Default Description
ArgLdMaxEd2 5 - 70 Deg 1 70 Maximum settable angle determining the
load impedance area, for 61850 Ed.2
settings
RLdFwMinEd2 0.01 - 5000.00 Ohm/p 0.01 0.01 Minimum settable resistance determining
the load impedance area, for 61850 Ed.2
settings
RLdFwMaxEd2 0.01 - 5000.00 Ohm/p 0.01 5000.00 Maximum settable resistance determining
the load impedance area, for 61850 Ed.2
settings
7.9.6 Monitored data
PID-6488-MONITOREDDATA v2
Table 154: ZMFCPDIS (21) Monitored data
Name Type Values (Range) Unit Description
A_Dir INTEGER 1=Forward
2=Reverse
0=No direction
- Direction in phase A
B_Dir INTEGER 1=Forward
2=Reverse
0=No direction
- Direction in phase B
C_Dir INTEGER 1=Forward
2=Reverse
0=No direction
- Direction in phase C
ABDir INTEGER 1=Forward
2=Reverse
0=No direction
- Direction in loop AB
BCDIR INTEGER 1=Forward
2=Reverse
0=No direction
- Direction in looop BC
CADir INTEGER 1=Forward
2=Reverse
0=No direction
- Direction in loop CA
Aph_R REAL - Ohm Resistance in phase A
Aph_X REAL - Ohm Reactance in phase A
Bph_R REAL - Ohm Resistance in phase B
Bph_X REAL - Ohm Reactance in phase B
Cph_R REAL - Ohm Resistance in phase C
Cph_X REAL - Ohm Reactance in phase C
ZAIMAG REAL - Ohm ZA Amplitude, magnitude of
instantaneous value
ZAANGIM REAL - deg ZA Angle, magnitude of instantaneous
value
ZBIMAG REAL - Ohm ZB Amplitude, magnitude of
instantaneous value
Table continues on next page
Section 7 1MRK 502 066-UUS B
Impedance protection
340
Technical manual