Name Type Description
SLIPZPER REAL Slip impedance in percent of ZBase
VCOS REAL UCosPhi voltage
VCOSPER REAL VCosPhi voltage in percent of VBase
7.10.5 Settings
PID-3526-SETTINGS v3
Table 158: PSPPPAM (78) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Enable / Disable
OperationZ1 Disabled
Enabled
- - Enabled Operation Enable/Disable zone Z1
OperationZ2 Disabled
Enabled
- - Enabled Operation Enable/Disable zone Z2
ImpedanceZA 0.00 - 1000.00 % 0.01 10.00 Forward impedance in % of Zbase
ImpedanceZB 0.00 - 1000.00 % 0.01 10.00 Reverse impedance in % of Zbase
ImpedanceZC 0.00 - 1000.00 % 0.01 10.00 Impedance of zone1 limit in % of Zbase
AnglePhi 72.00 - 90.00 Deg 0.01 85.00 Angle of the slip impedance line
pick up Angle 0.0 - 180.0 Deg 0.1 110.0 Rotor angle for the pickup signal
TripAngle 0.0 - 180.0 Deg 0.1 90.0 Rotor angle for the trip1 and trip2 signals
N1Limit 1 - 20 - 1 1 Count limit for the trip1 signal
N2Limit 1 - 20 - 1 3 Count limit for the trip2 signal
Table 159: PSPPPAM (78) Group settings (advanced)
Name Values (Range) Unit Step Default Description
ResetTime 0.000 - 60.000 s 0.001 5.000 Time without slip to reset all signals
Table 160: PSPPPAM (78) Non group settings (basic)
Name Values (Range) Unit Step Default Description
MeasureMode PosSeq
AB
BC
CA
- - PosSeq Measuring mode (PosSeq, AB, BC, CA)
InvertCTcurr No
Yes
- - No Invert current direction
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Section 7 1MRK 502 066-UUS B
Impedance protection
370
Technical manual