IEC06000437_2_en.vsd
IED
B A
E
B
E
A
X’
d
X
T
X
S
Zone 1 Zone 2
jX
R
X’
d
X
T
X
S
B
A
d
Apparent generator
impedance
Pole slip
impedance
movement
IEC06000437 V2 EN-US
Figure 196: Movements in the impedance plain
where:
X'
d
= transient reactance of the generator
X
T
= short-circuit reactance of the step-up transformer
Z
S
= impedance of the power system A
The detection of rotor angle is enabled when:
the minimum current exceeds 0.10 I
N
(I
N
is
IBase
parameter set under general setting).
the maximum voltage falls below 0.92
VBase
the voltage Ucosφ (the voltage in phase with the generator current) has an angular velocity of
0.2...8 Hz and
the corresponding direction is not blocked.
Section 7 1MRK 502 066-UUS B
Impedance protection
372