ZREFRE
is the real part (resistance) of the active reference impedance.
ZREFIM
is the imaginary part (reactance) of the active reference impedance.
VRMSSTAT, this output is not used in rotor protection application.
ERRSTAT output signal
Convert the integer output signal to binary and see table below for interpretation of individual
bits:
Table 186: Definition of errors
ERRSTAT output integer
Priority 3 Priority 2 Priority 3 Priority 1
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Interfer-
ence
detected
Under-
current
Under-
voltage
Over-
current
Over-
voltage
Frequ-ency
difference
No current No voltage
The ERRSTAT description will be shown in clear text in ICT.
The priority of the signals is set that the group priority 1 overrides the group priority 2 and 3, and
priority 2 overrides priority 3. Note that the ERRSTAT signal can enable several error cases at the
same time.
Following errors is detected and derived in the Error block:
B0 = Injected voltage signal not found
B1 = Injected current signal not found
B2 = Voltage and current signal frequency differs
B3 = Measured total RMS voltage too high
B4 = Measured total RMS current too high
B5 = Injected voltage signal too low
B6 = Injected current signal too low
B7 = External interference voltage detected
ERRSTAT = BitToInt[B7,…,B1,B0] The priority of the error conditions that will be flagged out:
Prio1 = B0, B1
Prio2 = B3, B4, B5, B6
Prio3 = B2, B7
RFAULT output signal
The injection equipment provides calculation of the fault resistance:
If the fault resistance is equal or below 10 kΩ, RFAULT displays the evaluated resistance to
earth in ohm
If the fault resistance is above 10 kΩ, RFAULT displays initially the code “-1000” until the
evaluated resistance to earth reaches a stable value, that is displayed in ohm
If an error condition is active, RFAULT displays the code “-2000”
7.13.8 Operation principle