PID-6519-OUTPUTSIGNALS v5
Table 205: PHPIOC (50) Output signals
Name Type Description
TRIP BOOLEAN Trip signal from any phase
TR_A BOOLEAN Trip signal from phase A
TR_B BOOLEAN Trip signal from phase B
TR_C BOOLEAN Trip signal from phase C
8.1.5 Settings
IP11434-1 v2
PID-6519-SETTINGS v5
Table 206: PHPIOC (50) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
OpModeSel 2 out of 3
1 out of 3
- - 1 out of 3 Select operation mode (2 of 3 / 1 of 3)
Pickup 5 - 2500 %IB 1 200 Phase current pickup in % of IBase
Table 207: PHPIOC (50) Group settings (advanced)
Name Values (Range) Unit Step Default Description
MultPU 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level
Table 208: PHPIOC (50) Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Table 209: PHPIOC (50) Non group settings (advanced)
Name Values (Range) Unit Step Default Description
PU_MinEd2Set 5 - 2500 %IB 1 5 Minimum settable operate phase current
level in % of IBase, for 61850 Ed.2 settings
PU_MaxEd2Set 5 - 2500 %IB 1 2500 Maximum settable operate phase current
level in % of IBase, for 61850 Ed.2 settings
Section 8 1MRK 502 066-UUS B
Current protection
448
Technical manual