If the current is still above the set value of the minimum operating current (between 10 and
30% of the set terminal rated current
IBase
), the condition seals in.
If the fault has caused tripping, the trip endures.
If the fault was detected in the reverse direction, the measuring element in the reverse
direction remains in operation.
If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.
The directional setting is given as a characteristic angle
AngleRCA
for the function and an angle
window
ROADir
.
Section 8 1MRK 502 066-UUS B
Current protection