100305
IMagComp5
IMagComp30
IMagComp100
-10
+10
Magnitude
compensation
% of In
Measured
current
% of In
0-5%: Constant
5-30-100%: Linear
>100%: Constant
100305
IAngComp5
IAngComp30
IAngComp100
-10
+10
Angle
compensation
Degrees
Measured
current
% of In
ANSI05000652_3_en.vsd
ANSI05000652 V3 EN-US
Figure 295: Calibration curves
The first current and voltage phase in the group signals will be used as reference and the
amplitude and angle compensation will be used for related input signals.
Analog outputs from the function can be used for service values or in the disturbance report. The
active power is provided as MW value: P, or in percent of base power: PPERCENT. The reactive
power is provided as Mvar value: Q, or in percent of base power: QPERCENT.
8.12.8 Technical data
SEMOD175160-1 v1
SEMOD175159-2 v8
Table 291: GOPPDOP (32) technical data
Function Range or value Accuracy
Power level
for Step 1 and Step 2
(0.0–500.0)% of SBase
When measuring transformer inputs
are used, the following accuracy can
be obtained for low pickup settings
which are typical for reverse power
protection application:
±1.0% of S
n
at S ≤ S
n
±1.0% of S at S > S
n
Pickup value=0.5% of S
n
Pickup accuracy of ±0.20% of S
n
*)
Pickup value=0.2% of S
n
Pickup accuracy of ±0.15% of S
n
*)
where S
n
= 1,732*V
n
*I
n
Characteristic angle
for Step 1 and Step 2
(-180.0–180.0) degrees ±2.0 degrees
Trip time, pickup at 0.5 to 2 x S
r
and
k
=
0.000
Min. =10 ms
Max. = 25 ms
Table continues on next page
1MRK 502 066-UUS B Section 8
Current protection
557
Technical manual